Flatpack S System

The increasing demand for higher bandwidths and the growing complexity of networks require flexible and expandable DC power supply solutions. Due to its low installation height (1U), high efficiency and effectiveness, reliability and wide range of applications, the Flatpack S system is the key to future requirements. Due to the low installation depth, the systems are very well suited for installation in most 19″ cabinets according to the ETSI standard and are therefore an excellent replacement solution for existing installations.

1 CONTROLLER + 2 RECTIFIERS and 1 CONTROLLER + 3 RECTIFIERS
Key Features of the Flatpack S System
 
  • Complete system
    • Smartpack S control unit
    • Rectifiers
    • Battery Distribution
    • Load distribution
  • 262 mm system depth
  • 1U Height
  • Hot Pluggable Rectifiers
  • Hot Pluggable Controller
  • Advanced control and monitoring via Ethernet ports
  • 2R (40A) Load Options
    • 7 x 30A MCB Slots (Optional LVLD)
    • 4 x 30A MCB Front
    • 7 x 15A Fuses Front
  • 3R (100A) Load Options
    • 2 x 80A
Flatpack S 48V 1800W Rectifier
Smartpack S Controller
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Input data 100 – 250VAC 100 – 250VAC
Mains Configuration 230VAC, 1 phase or 2 x 1phase 230VAC, 3 x 1 phase or 3 phase(∆) 230/400VAC, 3 phase (Y)
Mains Connection 2,5mm2 Terminal blocks, rear connection 2,5mm2 Terminal blocks, rear connection
Frequency 45 to 66Hz 45 to 66Hz
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Voltage – 48VDC – 48VDC
Max.
Current
40A 100A
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
LVBD Default Default
Breaker (Plug-in type) maximum size 2 x 40A1) 2 x 80A1)
Connection (rear) 16mm2 Terminal blocks M6 cable lug
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Rear connections N/A 2 x 80A, M6 cable lug
Rear cabel entry, front access Connections, screw terminals Optional LVLD 7 x 30A MCB2)) N/A
Rear cabel entry, front access Connections, screw terminals Optional LVLD 7 X 4mm2 N/A
Rear cabel entry, front access Connections, screw terminals Optional LVLD on MCB 1 and 2 N/A
Rear cabel entry, front access Connections, screw terminals Optional LVLD 4 x 30A MCB / 7 x 15A Fuse 4mm2 N/A
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Smartpack S 6x Input/Output and Ethernet, See Smartpack S datasheet 6x Input/Output and Ethernet, See Smartpack S datasheet
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Dimensions (W/H/D) 19″/1U/262mm Recommended minimum cabinet depth, 300 mm 19″/1U/262mm Recommended minimum cabinet depth, 300 mm
Weight, including controller and distributions, excluding rectifiers 5.2 kg [11 .5 lbs] 5.3 kg [11 .7 lbs]
Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Dimensions (W/H/D) 19″/1U/262mm Recommended minimum cabinet depth, 300 mm 19″/1U/262mm Recommended minimum cabinet depth, 300 mm
Weight, including controller and distributions, excluding rectifiers 5.2 kg [11 .5 lbs] 5.3 kg [11 .7 lbs]

,

Model 1 Controller + 2 Rectifiers 1 Controller + 3 Rectifiers
Electrical safety UL 60950-1, EN 60950-1 UL 60950-1, EN 60950-1
EMC ETSI EN 300 386 V.1.4.1
EN 61000-6-1 (immunity, light industry)
EN 61000-6-2 (immunity, industry)
EN 61000-6-3 (emission, light industry)
EN 61000-6-4 (emission, industry)
ETSI EN 300 386 V.1.4.1
EN 61000-6-1 (immunity, light industry)
EN 61000-6-2 (immunity, industry)
EN 61000-6-3 (emission, light industry)
EN 61000-6-4 (emission, industry)
Environment ETSI EN 300 019-2-1 Class 1.2
ETSI EN 300 019-2-2 Class 2.3
ETSI EN 300 019-2-3 Class 3.2
ETSI EN 300 019-2-1 Class 1.2
ETSI EN 300 019-2-2 Class 2.3
ETSI EN 300 019-2-3 Class 3.2
1) If only one string is used, one of the battery breakers can be configured as a load breaker.
2) Drawer solution, front access for actual connection, but cables enters from rear